Electricity Type: | AC |
---|---|
Number of Pole: | 3p, 4p |
Phase: | 3 |
Type: | Ac Contactors |
Model: | D09, D12, D18, D25, D32 |
Rated Conventional Heating Current: | 20, 32, 40, 50 |
Customization: |
---|
Suppliers with verified business licenses
Specification | ||||||||||
Type |
220V 230V KW |
380V 400V KW |
660V 690V KW |
200V 440V HP |
240V 500V HP |
460V HP |
600V HP |
AC-3 440V |
NO |
NC |
ELC1-D0910/W | 2.2 |
4 |
4 |
4 |
5.5 |
5.5 |
- |
9 |
1 _ |
- 1 |
ELC1-D0901/W | ||||||||||
ELC1-D1210/W | 3 |
5.5 |
5.5 |
5.5 |
7.5 |
7.5 |
- |
12 |
1 - |
- 1 |
ELC1-D1201/W | ||||||||||
ELC1-D1810/W | 4 |
7.5 |
9 |
9 |
10 |
10 |
- |
18 |
1 - |
- 1 |
ELC1-D1801/W | ||||||||||
ELC1-D2510/W | 5.5 |
11 |
11 |
11 |
15 |
15 |
- |
25 |
1 - |
- 1 |
ELC1-D2501/W | ||||||||||
ELC1-D3210/W | 7.5 |
15 |
15 |
15 |
18.5 |
18.5 |
- |
32 |
1 - |
- 1 |
ELC1-D3201/W | ||||||||||
Items Model | D09 |
D12 |
D18 |
D25 |
D32 |
|||||
Rated conventional heating current(A)AC-1 | 20 | 20 | 32 | 40 | 50 | |||||
Rated insulation voltage(V) | 690 | 690 | 690 | 690 | 690 | |||||
Electric AC-3 | 1200 | 1200 | 1200 | 1200 | 1200 | |||||
Operating frequency Life AC-4 (operations/h) |
300 |
300 |
300 |
300 |
300 |
|||||
Mechanical life | 3600 | 3600 | 3600 | 3600 | 3600 | |||||
Electric life AC-3 (X 103 operations) AC-4 |
1000 200 |
1000 200 |
1000 200 |
1000 200 |
1000 200 |
|||||
Mechanical life(X 106 operations) | 10 | 10 | 10 | 10 | 10 | |||||
Matched fuse type | RT16-20 | RT16-20 | RT16-32 | RT16-40 | RT16-50 |